Tag: 01-FM-1

Flow Switch

Flow Switch
FLOW SWITCH
Make Dwyer Instruments
Model Flotect V6
Service Gases or liquids compatible with wetted materials
Wetted Materials
  • Standard V6
  • Models: Vane: 301 SS
  • Lower Body: brass or 303 SS
  • Magnet: ceramic
Temperature Limits -4 to 220°F (-20 to 105°C) Standard, MT high-temperature option 400°F (205°C)
Pressure Limit Brass lower body with no tee models: 1000 psig (69 bar)
Enclosure Rating Weatherproof and Explosion-proof. Listed with UL and CSA for Class I, Groups A, B, C, and D; Class II, Groups E, F, and G
Switch Type SPDT snap switch standard, DPDT snap switch optional
Upper Body Brass or 303 stainless steel
Process Connection 1/2" (12.70 mm) male NPT or 1/2" (12.70 mm) male BSPT on models without a tee.
Agency Approvals ATEX, CE, CSA, IECEx, KTL, UL