Tag: 01-PG-19

Differential Pressure Gauge – Capsule Type
Differential Pressure Gauge - Capsule Type
DIFFERENTIAL PRESSURE GAUGE - CAPSULE TYPE
For differential pressure measurement of non-corrosive, gaseous, dry media. Especially suitable for filter loss measurement in air conditioning and ventilation applications.
Make AFRISO EUROINDEX GMBH
Accuracy class (EN 837-3/6) 1.6 (< 10 mbar: 2.5)
Connection Brass, bottom or centre back; parallel in line
Dial Aluminum, white; Dial marking black (bar/mWC)
Housing Stainless steel 304
Seal NBR (Perbunan)
Degree of protection IP 32 (EN 60529)
Nominal size 63 – 100 – 160
Operating temperature range
  • Medium: Tmax = +60 °C
  • Ambient: Tmin = -20 °C
  • Tmax: +60 °C
Ranges (EN 837-3/5) NG 63 0/16 to 0/400 mbar, NG 100 0/6 to 0/400 mbar, NG 160 0/4 to 0/400 mbar
Bayonet type bezel/crimped bezel: Stainless steel 304